ICID Plus – Twin Wall Insulated System Chimney

Our Eco ICID range has evolved into a multi-application system adaptable for Dry (D), Fu (W) and even Positive Pressure (P) applications.

Feel free to select the various options shown below, with Internal and External installation and a combination of Single Wall to Double Wall. You can also download the PDF version of the Installation Instructions to your phone or device.

Download Manual (PDF)

APPROVAL

ICID Plus is CE Certified to EN1856-1 TUV 0036 CPR 9195 010 with designations: ICID Plus is CE Certified to EN1856-2 TUV 0036 CPR 9195 042 with designations:

System Chimney EN1856-1

T450 N1 W V2 L50050 G60

T450 N1 D V3 L50050 G60

60mm Distance to combustibles running through a combustible floor using G60 round firestop

T450 N1 W V2 L50050 G50

T450 N1 D V3 L50050 G50

50mm Distance to combustibles a) running through a combustible floor using G50 ventilated fire stops b) In a ventilated shaft using G50 or G60 round ventilated fire stops in combination with G50 ventilated support plate at base and G50 ventilated fire stop plate at top of shaft. c) In free air

T200 P1 W V2 L50050 O00

Zero distance to combustibles*

Connecting Flue Pipe EN1856-2

T450 N1 D V2 L50050 G100 M

* For full information please see Distance to Combustibles Section

  • Manufactured under a Quality Management Scheme approved to BS EN ISO 9001
  • 4 Hour Fire Rating to BS476 Part 20
  • Certified for corrosion resistance on gas, oil and solid fuel by Gastec, MPA and TUV
  • HETAS listed for use on solid fuel applications.

DESIGN GUIDE

Mandatory Requirements

Connection to an appliance which is not connected to the fuel supply, should be carried out by a competent person. We recommend the use of HETAS approved installers for solid fuel applications. If installation is carried out by a non HETAS registered installer, the installation must be certified by a local Building Control inspector. Connection to an appliance that is connected to the fuel supply must be carried out by a Gas Safe (Gas) or OFTEC (Oil) registered installer.

The design guide must be read in conjunction with the detailed component installation instructions. For full design and installation details the key referral documents are:

  • BS EN 1856-1: Chimneys – System Chimney Products
  • BS EN 1856-2: Connecting Flue Pipes
  • BS EN 1859: Metal Chimneys – Testing Methods
  • BS EN 1443: Chimneys – General Requirements
  • BS EN 15287-1: Chimneys. Design, installation and commissioning of chimneys. Chimneys for non-room sealed heating appliances.
  • BS 5440-1: Fluing and ventilation for gas appliances of rated input not exceeding 70kW net (Ist, 2nd and 3rd family gases). Specification for installation of gas appliances to chimneys and for maintenance of chimneys.
  • Approved Document J: – Combustion appliances and fuel storage systems (England & Wales)
  • DFP Technical Booklet L:: – Combustion appliances and fuel storage systems (NI)
  • Technical Handbook (Domestic & Non Domestic), Section 3 – Environment (Scotland)
  • Appliance Installation Instructions and related standards. Other standards covering specific applications will also be relevant and must be adhered to.

Planning permission may be required, and reference should be made to the local Building Control Department.

Ensure all chimney components are available and check them to ensure there has been no damage. Do not use damaged components. Build the chimney up through the previous designed route which should be as straight as possible.

PRIOR TO INSTALLATION

Ventilation

It is very important that sufficient air for combustion and ventilation is provided to the room containing the appliance, to enable correct and efficient working of the appliance and chimney system. Reference should be made to the appliance manufacturer’s instructions and recommendations are also given in the Building Regulations Document J, CIBSE guidance notes and BS 5440.

Carbon Monoxide Alarms

The carbon monoxide alarms should comply with BS EN 5029I

Where a new or replacement fixed solid fuel appliance is installed in a dwelling, a carbon monoxide alarm must be provided in the room where the appliance is located.

Please follow manufacturers instructions with regards to siting and fixing or alternatively :-

  1. On the ceiling at least 300mm from any wall or if it is located on a wall, as high up as possible (above any doors and windows), but not within I50mm of the ceiling and

  2. between Im and 3m horizontally from the appliance.

N.B Provision of a carbon monoxide alarm should not be regarded as a substitute for correct installation and regular servicing.

Painting

If painting of any external sections is required, it is important to de-grease, dry and prime the exterior surface prior to the application of appropriate heat resistant paint. Schiedel Chimney Systems can provide to special order, chimney sections and accessories painted to an extensive range of British Standard RAL colours – details on application.

Handling

It is advised that suitable PPE should be used when handling the products.

Delivery to Site and Storage

Components should be carefully transported and off loaded.They should be inspected to ensure they have not been damaged, and should be stored off the ground and under cover so that they are protected from accidental damage and the adverse effects of weather.

CONNECTING FLUE PIPE

Appliance/Chimney Connection

Connection to the appliance can be made using Prima Smooth, Prima Plus or alternative approved single wall connecting flue pipes, or ICID Plus. This must be done by using the appropriate appliance connector. When a single wall connecting flue pipe is used to connect an appliance to the chimney, the lower end of the chimney section must extend a minimum of 425mm below the ceiling. When connecting the appliance to the flue pipe all joints between the flue pipe/appliance outlet must be securely caulked and sealed with non asbestos rope (or suitable alternative) and fire cement on solid fuel appliances. Any flue pipe connection to the chimney MUST be made in the same room as the appliance.

Provision for Condensate Disposal (subject to appliance manufacturers’ recommendations) 

Condensing appliances need provision for drainage. Choose the appropriate flue drainage components normally fitted at the base of the vertical stack and/or close to the appliance outlet. Any ‘horizontal’ runs must allow for a minimum 3° slope and therefore, where required, 87° bends and 93° tees must be used rather than 90° bends and tees.

Connection to Draught Diverter

Where the appliance features a draught diverter the connection should rise vertically from it for at least 600mm before any change of direction (unless otherwise specified by the appliance manufacturer). This is in accordance with the recommendations contained in BS 5440 Part 1 section 6.1.4

Connecting Flue Pipe Diameter

Connecting Flue Pipe Diameter size should be as recommended by the appliance manufacturer. Under all circumstances the operational requirements of the appliance and the configuration of the flue must satisfy the flue sizing requirements of EN13384-1.

Distance to Combustibles

In accordance with building regulations, it is essential that the correct distance to combustible material is maintained on connecting flue pipes. On solid fuel applications, where there is a risk of soot fire, on unmeasured (NM) designated single wall product, this distance is 3 x 0Int of the pipe, e.g. for 0125mm the distance is 375mm and for 0150mm the distance is 450mm to combustibles on both painted and non painted variants. On measured (M) single wall or double wall products this distance will be as declared by the chimney manufacturer. On ICID Plus this distance has been measured and is set at 100mm.

Connecting Flue Pipe Route

Single wall connecting flue pipes should only be used to connect appliances to a Chimney.They should not pass through any roof space, partition, internal wall or floor, except to pass directly into a chimney through a wall of the chimney. Connecting flue pipes should be located as to avoid igniting combustible material. On solid fuel appliances the maximum length of a connecting flue pipe is 2m.This distance is reduced to 1.5m if any of the acceptable alternative methods of connection are adopted as per BS EN15287-1. (See p.5-6 for full details.) On appliances with a top outlet, it is recommended that a vertical run of at least 600mm should be allowed immediately above the appliance prior to any change of direction. On appliances with a rear outlet, it is recommended that there is maximum of 150mm in the horizontal run however under certain conditions, as described in alternative methods in BS EN 15287-1, this may be increased to 450mm. (See p.5-6 for full details.) Within a system (Chimney + Connecting Flue Pipe) there should be no more than 4 changes of direction of maximum 45°. 90° Factory made bends or tees within the system may be treated as being equal to two 45° bends (as per Document J of the Building Regulations issued October 2010).

Inspection

On solid fuel applications to conform to Building Regulations, provisions should be made to enable a chimney to be inspected and cleaned. An inspection pipe, inspection elbow or a 90° or 135° Tee with tee cap can form a suitable inspection point (unless cleaning/inspection can be done through the appliance).To aid cleaning, sufficient distance should be left between changes of direction to permit the safe passage of cleaning brushes within the system.This is particularly important on solid fuel applications. It is recommended that chimneys serving solid fuel appliances be swept as frequently as necessary, but at least twice a year.

BS EN 15287-1 ACCEPTABLE ALTERNATIVE METHODS OF CONNECTION

Where a horizontal connecting flue of more than 150mm is required to connect a solid fuel fired appliance to a chimney, an installation method as per the examples below may be used provided the following criteria is met:-

  1. The maximum length of horizontal connecting flue pipe does not exceed 450mm;

  2. A Defra exempt appliance or an appliance, which is limited to burning authorised smokeless fuel only, is installed;

  3. A calculation according to BS EN13384-1 has indicated safe operation of the proposed configuration, and the results of the calculation are left with the householder along with the appliance installation instructions;

  4. The appliance manufacturer agrees in writing to the proposed configuration;

  5. The chimney manufacturer agrees in writing to the proposed configuration;

  6. The total length of single wall connecting flue pipe is not more than 1.5m;

  7. The appropriate distances to combustible materials from both the appliance and the connecting lue pipe are maintained.

NOTE: These alternative methods do not apply to Republic of Ireland.

Rear Outlet Twin Wall Connecting Flue Pipe into Re-lined Masonry Chimney

Top Outlet Twin Wall Connecting Flue Pipe into Re-lined Masonry Chimney

Top Outlet Twin Wall Connecting Flue Pipe through Solid Wall into Twin Wall System Chimney

 

Top Outlet Single Wall Connecting Flue Pipe through Solid Wall into Twin Wall System Chimney

NB Where the connecting flue pipe from the appliance passes through any wall other than the existing chimney wall, the connecting flue pipe must be a System Chimney of twin wall insulated design.

Rear Outlet Twin Wall Connecting Flue Pipe Through Cavity Wall into Twin Wall System Chimney

Rear Outlet Twin Wall Connecting Flue Pipe into External Masonry Chimney through a Cavity Wall

SYSTEM CHIMNEY

Chimney Diameter

The chimney size should be as recommended by the appliance manufacturer. Where there is a requirement for a flue diameter smaller than the appliance spigot, then the operational requirements of the appliance and the configuration of the flue must satisfy the flue sizing requirements of EN13384-1 for single appliances, and EN13384-2 for multi appliances.

Chimney Route

The chimney should remain as straight as possible through its vertical run to assist flow. Should it be necessary to offset a chimney run then the following guidelines should be adhered to: It is recommended that a vertical run of at least 600mm should be allowed immediately above the appliance prior to any change of direction.Within a system, on all fuels, there should be no more than 4 changes of direction of maximum 45°. Factory made 90° bends or tees within the system may be treated as being equal to two 45° bends (as per Document J of the Building Regulations issued October 2010).

Connection to Draught Diverter

Where the appliance features a draught diverter the connection should rise vertically from it for at least 600mm before any change of direction (unless otherwise specified by the appliance manufacturer). This is in accordance with the recommendations contained in BS 5440 Part 1 section 6.1.4

Direct Connection Appliance to System Chimney

When connecting from the appliance directly to a system chimney, the appropriate appliance connector must be used and the joint between the appliance spigot and the appliance connector must be securely caulked and sealed with non asbestos rope (or suitable alternative) and fire cement on solid fuel appliances.

Distance to Combustibles

In accordance with building regulations, it is essential that the correct distance to combustible material is maintained. On solid fuel applications, where there is a risk of soot fire, a distance of 60mm to combustibles must be maintained within a combustible floor and within a combustible shaft (see Fig.1 below).There is no need to line the area within the floor cavity with plasterboard; however the ventilated ire stop plate and ventilated support plate must be used. On gas and oil applications, a distance of 50mm to combustibles must be maintained within a combustible loor and within a combustible shaft. The ventilated ire stop plate and ventilated support plate must be used. Where the chimney penetrates a non combustible floor and where a non combustible shaft is used, a distance of 50mm to the shaft is sufficient. In this case, non ventilated ire stop plates and support plates may be used with a ventilated ire stop being used where the chimney penetrates into the roof space. On bungalow applications where the chimney runs through either a combustible or non-combustible ceiling, an unventilated bungalow fire stop plate kit can be used. Please note that an unventilated support plate can not be used above the ceiling in this case. The weight of the chimney should be supported using the roof support (see p.I9). Distance to combustibles must be respected within the ceiling space (see Fig. 2 below) and mesh frame should be used within the loft space, which must be ventilated (see Fig. 2 below).

Enclosure/Shafts

With the exception of the room containing the appliance, where the chimney passes through any part of the building, where there is a risk of accidental human contact, i.e a bedroom etc., or where there is a risk of contact with combustible materials stored in a cupboard or in the roof-space, the chimney must be enclosed in an appropriate way to meet Building Regulations. This can be achieved by boxing in the chimney in habitable rooms, or by the use of a protective wire mesh frame in roof spaces etc. In all cases the minimum distance to any combustible material, including loft insulation, must be respected according to the table on p.I, and any enclosure should be ventilated using the appropriate ventilated fire stops (see p.I3).

Support Components

The weight of a chimney system is considerable and requires independent support. Minimal weight should be borne by the appliance.The weight of the chimney can be supported from floor level by using a base support plate, or floor support; from the wall by using wall support top plates together with side plates or cantilever brackets; or from first floor level by using a support plate and clamp fixed to the floor/ceiling joists. Wall brackets are non load bearing and provide lateral support only. Refer to the load bearing tables on page 33 for full details of maximum loadings. Where the flue is freestanding above the roof and its height exceeds I.Sm above the last support or above the roof, a height of up to 3m can be achieved unsupported using the extended locking bands at the joint immediately below the last support and on each pipe joint above the last support. Alternatively guy wire brackets can be used at the I.Sm level and every I.Sm thereafter in conjunction with guy wires, or rigid stays (provided by others).

Chimney Termination

For full information regarding to chimney termination, please refer to Annex M of BS EN IS287-I. As a guide please refer to page 3I of these installation instructions.

Terminals

All terminals must be secured with the use of a locking band. On solid fuel appliances, an open termination is normally recommended. However in certain conditions, rain caps or anti-downdraught terminals may be used. Rain caps and anti-downdraught terminals are available in three versions, with anti-bird mesh, with spark guard, or without mesh. Where a terminal with mesh is used, there is a risk of soot build up, and therefore regular cleaning is required to avoid blockage, particularly when using oil or solid fuel.

INSTALLATION INSTRUCTIONS

Jointing System

All joints in the ICID Plus chimney range, which require a locking band, are made by means of a simple twist lock jointing method. This is achieved by pushing together the male and female collars on each end of the main chimney components and twisting the components through I/6 of a turn to lock the collars into place. It should be noted that the female collars on elbows and tees are not barbed in order to allow for these items to be positioned according to requirements on site. In all cases the joints should be held securely in place using the locking band, which is supplied with all components with a female collar.

Standard Chimney Sections (Pipes, Tees and Elbows)

Before assembling chimney sections, loosen the locking band by lifting the clip. Push the interlocking collars together and twist into position (see Fig.I). Position the locking band so that it grips both collars then fasten using the clip. Note:-joints must NOT occur within floor or ceiling spaces. All flue gas carrying components must be installed with the direction arrow on the product label pointing to termination with the external male collar uppermost.

A locking band must be fitted to every joint in the system. The band is of stainless steel construction and is fitted with a quick release clip.

Gasket Kits

The standard single female lip seal kit is used to convert standard fixed components with a male collar for use in condensing applications. The female lip seal must be fitted into the inward bead on the liner just below the male collar. Lubricant should be applied to the outside of the protruding liner of the next component to be fitted (see Fig.2) A separate gasket kit with 2 gaskets (I female and I male) and a sachet of lubricant is required for adjustable pipes. The female lip seal, with the lip on the inside is fitted, as per a standard component, into the inward bead as shown in Fig.2.The second male lip seal with the lip on the outside of the ring is fitted into the inward bead, which is situated in the top half of the 2-piece adjustable pipe (see Fig.3) and at the bottom of the I-piece adjustable pipe. N.B Where a I-piece adjustable pipe is used, then no female lip seal is required in the groove below the male collar of the preceding pipe.

On 2-Piece Adjustable Pipe a female lip seal is required on the preceding standard pipe to ensure leakage performance of the system. All lip seals to be added by installer.

On 1-Piece Adjustable Pipe no lip seal is required on preceding standard pipe, as a male lip seal (once added) will ensure leakage performance. All lip seals to be added by installer.

Structural Locking Band

The structural locking band, which is purchased separately, is used instead of a standard locking band in a situation where extra structural support is required, for instance where the chimney height is >I.Sm above the last support or above the roof. It is also used to provide extra support in long horizontal runs. A maximum of 3m unsupported height can be achieved by fitting the structural locking band on the joint immediately below and on every joint above the last support. Please see diagram on page 32.

Structural Locking Band for Bends

The structural locking band for Bend, which is purchased separately, is used instead of a standard locking band in a situation where extra structural support is needed in an offset.

Appliance Connector

  1. The protruding liner of these components should be pushed into the appliance spigot with the male collar pointing upwards. The liner can be trimmed to suit the depth of the appliance spigot.
  2. On solid fuel appliances the appliance connector should be sealed to the appliance with fire rope and fire cement or high temperature sealant to provide a gas tight joint.

Adaptors from Prima Plus & Prima Smooth to ICID Plus

These components are used to convert from a single wall connecting flue pipe to the ICID Plus system chimney. The protruding liner should be pushed down inside the female socket of the connecting flue pipe, with the male collar pointing upwards.

Adaptor to Flex/TecnoFlex Plus

This component is used to convert from ICID Plus to Flex/TecnoFlex Plus.The Flex/TecnoFlex Plus is pushed down inside the upstand on the adaptor, secured using self tapping screws and sealed with fire cement and fire rope to provide a gas tight joint.

Adaptor from ICID Plus to Prima Plus

This component is manufactured with an ICID Plus female collar and a Prima Plus female socket, and is used where there is a requirement to convert from ICID Plus to Prima Plus. The ICID Plus female collar should be attached to the previous ICID Plus component and the joint secured using the locking band provided.

Adaptor from ICID Plus to Prima Smooth

This component is manufactured with an ICID Plus female collar and a Prima Smooth female socket, and is used where there is a requirement to convert from ICID Plus to Prima Smooth. The ICID Plus female collar should be attached to the previous ICID Plus component and the joint secured using the locking band provided.

SW-DW Stove Pipe Starter Section

This component is used to connect from a vitreous enamel or stainless steel single wall connecting flue pipe to ICID Plus. The protruding liner should be pushed down inside the female socket of the connecting flue pipe and the joint sealed with fire cement or high temperature sealant to provide a gas tight joint. Please note that when a single wall connecting flue pipe is used to connect to the starter section, the joint between these two components must be a minimum of 425mm below the ceiling in accordance with BS EN 15287-1. This component MUST only be fitted to stove pipe and NOT directly to appliance.

SW-DW Adjustable Starter Section

The protruding male spigot of the adaptor slides down inside the female socket of the Prima Smooth pipe and the socket of the Prima Smooth pipe slides within the conical section of the starter adaptor, to a maximum length of 75mm into the cone with a minimum of 15mm to ensure a secure connection. This maximum length of 75mm will leave sufficient space within the adaptor to allow for thermal expansion of the single wall pipe and also to allow for the connecting flue pipe to be removed without cutting, if the appliance has to be moved for servicing. This component MUST only be fitted to stove pipe and NOT directly to appliance.

Double Wall Adjustable Starter Section

Increaser

This component is used to increase from one diameter to the next diameter (e.g.) 125mm to 150mm. The component is fitted in the same way as a standard pipe length and should be secured with the locking band provided.

Anchor Plate Anchor Plate When commencing an installation with a fire chest, or when extending an existing brick or masonry chimney stack, an anchor plate must be used. The liner of the Anchor Plate should be pushed into the opening of the fire chest with the plate resting on a bed of fire cement. The plate should then be fixed onto the concrete slab by masonry screws fitted through the pre-drilled holes in the plate. In the case of a chimney extension, the liner of the anchor plate fits down inside the existing chimney stack, or if TecnoFlex Plus liner has been used, inside the chimney as a liner, use the anchor plate with screw type connections. Refer Flexible Liners installation instructions for more details. The plate should then be then be fixed to the top of the existing chimney and sealed using fire cement.

Adjustable Pipe/Telescopic Pipes

They are used with standard components to achieve an exact length on site and avoid on-site cutting of components.

  1. Calculate the length required.
  2. Remove insulation as required to achieve the correct length.
  3. Fix the adjusted section to standard components using the locking band provided.

Please note that the adjustable pipe is non load bearing.

When used in a condensing or a positive pressure application, the relevant gasket kits must be applied by the installer (gaskets purchased separately). Follow Page 11 for instructions on Gasket Kits.

Inspection Pipe with Test Point

The inspection length is a component providing the facility for flue inspection and cleaning, including a test point. It is installed as per a standard pipe section. Two versions available for Dry and Wet systems.The removable inspection door must be parallel with the front of the stove, or at least 3 x the internal diameter from any combustible material (125mm I/D door must be at least 450mm from combustible material). Note: The removable inspection door must be parallel with the front of the stove, or at least 3 x the Internal diameter form any combustible material (125mm I/D Door must be at least 450mm from combustible material)

90° Tee including Drain Cap

This component may be used to connect from a connecting flue pope to the vertical system chimney at 90° or the branch may be used to locate a draft stabiliser. It is installed as per a standard pipe section. Please note that there are no barbs on the female collar in order to allow for the tee to be positioned at the correct angle. It is supplied complete with a locking plug.

Int Ø

100

125

150

180

200

Ext Ø

150

180

200

235

256

A (mm)

282

301

329

354

394

B (mm)

150

154

162

176

195

C (mm)

120

133

142

160

170

93˚ Tee including Drain Cap

This component must be used in place of a 90° tee to connect from a connecting flue pipe to the vertical System Chimney on condensing systems to ensure that condensate can drain down through the system to a drain point.This component is installed as per a standard pipe section.

Int Ø

100

125

150

180

200

Ext Ø

150

180

200

235

256

A (mm)

285

297

322

356

396

B (mm)

155

158

166

180

201

C (mm)

121

136

147

167

177

135° Tee including Drain Cap

There are 2 versions of the 135˚ tee available. The condensing version has a fully welded liner, so please ensure, prior to installation on a condensing appliance, that you have the fully welded version to hand.

This component may be used in combination with a 45° elbow to connect from a connecting flue pipe to the vertical system chimney. It is installed as per a standard pipe section and provides the least resistance to the flow of the flue gases. Please note that there are no barbs on the female collar in order to allow for the tee to be positioned at the correct angle. It is supplied complete with a drain plug.

Int Ø

100

125

150

180

200

Ext Ø

150

180

200

235

256

A (mm)

325

336

365

414

444

B (mm)

254

259

283

326

351

C (mm)

254

259

283

326

351

Elbows and 90° Inspection Elbows

For offset information on standard elbows, please refer to p.18

Please note that 90 inspection bends may be incorporated into a connecting flue pipe arrangement on all fuels. Please refer to National Annex of BS EN 15387-1 for specific guidance re use on solid fuel applications.

In cases of top mounted stoves, a minimum vertical height of 600mm from the appliance is recommended prior to any change of direction in the flue pipe.

On condensing appliances 87° bends must be used rather than 90° bends where required in order to ensure correct run off of condensates.

OFFSET DIMENSIONS (made by assembling 2 bends)

Offsets for 15° Bend

Int 0

100

125

150

180

200

(mm)

228

232

234

234

238

(mm)

30

31

31

31

31

Offsets for 15° Bend with Standard Pipe Length

Int 0 (mm)

100

125

150

180

200

1460 Eff

Pipe

A B

1642

408

1644

409

1644

409

1648

409

960 Eff Pipe

A B

1155

278

1159

279

1161

279

1161

279

1165

280

750 Eff Pipe

A B

952

224

956

225

958

225

958

225

962

225

460 Eff Pipe

A B

672

149

676

150

678

150

678

150

682

150

293 Eff Pipe

A B

511

106

515

106

517

107

517

107

521

107

160 Eff Pipe

A B

383

71

387

72

388

72

388

72

392

73

 

Offsets for 30° Bend

Int 0

100

125

150

180

200

(mm)

228

230

244

256

271

(mm)

61

62

66

69

73

 

Offsets for 30° Bend with Standard Pipe Length

Int 0 (mm)

100

125

150

180

200

1460 Eff

Pipe

A B

1494

792

1509

796

1520

799

1535

803

960 Eff Pipe

A B

1059

541

1061

542

1076

546

1087

549

1102

553

750 Eff Pipe

A B

877

436

879

437

894

441

905

444

920

448

460 Eff Pipe

A B

626

291

628

292

643

296

654

299

669

303

293 Eff Pipe

A B

481

208

483

208

498

212

509

215

524

219

160 Eff Pipe

A B

366

141

368

142

383

146

394

149

409

153

 

Offsets for 45° Bend 

Int 0

100

125

150

180

200

(mm)

256

254

268

295

309

(mm)

106

105

111

122

128

 

Offsets for 135° Tee and 45° Bend

Int 0

100

125

150

180

200

(mm)

383

402

435

497

532

(mm)

303

310

334

376

402

 

Offsets for 45° Bend with Standard Pipe Length

Int 0 (mm)

100

125

150

180

200

1460 Eff

Pipe

A B

1287

1138

1300

1143

1328

1151

1341

1160

960 Eff Pipe

A B

935

785

933

784

947

790

974

801

988

807

750 Eff Pipe

A B

786

636

785

636

798

641

826

653

839

658

460 Eff Pipe

A B

581

431

580

431

593

436

621

448

634

453

293 Eff Pipe

A B

463

313

462

313

475

318

503

330

516

335

160 Eff Pipe

A B

369

219

367

218

381

224

408

235

422

241

FIRESTOP COMPONENTS

Ventilated Support Plate (Galvanised plate with S/S Band)

The support plate is used where the chimney passes through a combustible floor, and the weight of the chimney has to be taken at floor level. The support plate must be firmly fixed by using bolts or screws. For load bearing Data refer to tables 1 and 2 on page 41. 1. Frame a four sided level square opening within the joists using timber stringers where necessary to allow for the correct distance to combustibles from the outer wall of the chimney and for 6 fixing points. When using a G60 round ventilated Firestop Plate, this distance X must be a minimum of 50mm on Gas and Oil applications and 60mm for solid fuel applications (see Fig. 2 below). N.B if a G50 round ventilated plate is used this distance X will be a minimum of 50mm also for solid fuel applications 2. Lower the chimney section through the opening in the floor, and secure to the next section of pipe. 3. Locate the two halves of the support plates around the chimney section, and secure to the joists using screws or bolts. 4. Remove the self-drilling screws which are fastened to the clamp band. Then fasten clamp band around the chimney section and position on top of the plate. Tighten using the nuts and bolts provided. 5. Using the holes in the clamp band as a guide, fasten the three self-drilling screws to the outer case of the ICID Plus system.

Note: Joints must NOT occur within the floor or ceiling joists.

G60 Ventilated Firestop Plate (1& 2-Piece Round and 2-Piece Rectangular)

The ventilated fire stop plates are used in combination with standard ICID Plus pipes where the chimney passes through a combustible floor or ceiling. The outermost circle of ventilation slots gives a distance to combustibles of 60mm. This measures the required distance for solid fuel applications. For gas and oil applications a minimum of 50mm is required, which should be measured on site. The fire stop plate should be positioned around the chimney and fastened to the pre-cut plasterboard or to the timber frame with nails or screws using the location holes provided (see Fig. 2 above).

G50 Ventilated Firestop Plate (1 Piece Round and Rectangular)

Where the G50 round ventilated fire stop plate is used on the living room ceiling, the outermost slots give the required distance to combustibles of 50mm. This distance must be respected as the chimney passes through the ceiling and floor areas and through the shaft and ceiling penetration in the bedroom.

Magnetic Firestop Cover (Optional)

Can be used in combination with I-piece Ventilated Firestop Plate)

Non-Ventilated Bungalow Firestop

Installed as per a ventilated firestop using the fixing holes provided (see Fig.4 above). Distance to combustibles must be respected – see p.8 for further info.

Support Plate with S/S Clamp Band (Non Combustible Floor)

The support plate is used where the chimney passes through a non combustible floor, and the weight of the chimney has to be taken at floor level. The support plate must be firmly fixed to the floor using bolts or screws provided by others. For Load Bearing Data refer to table on page 33.

Fire stop Plate (Non Combustible Floor)

This fire stop plate is used exclusively where the chimney passes through a non combustible floor. The two halves of the plate are located around the chimney section and fastened to the floor using bolts or screws provided by others.

Retrofit Wall Band

  1. Slide bracket down of chimney to the required position.
  2. Once the position of the support has been determined, secure the back bracket to the wall with a method of fixing to ensure adequate attachment and support.
  3. The wall bracket provides lateral stability only, it is NOT load bearing and is to be positioned at 3 metre centres.

Wall Band (60mm)

Internal and External Application

The wall band is supplied in three parts, two stainless steel split bands which fit tightly around the outside of the chimney and a stainless steel back bracket.The parts are joined together by means of the nuts and bolts provided.The use of the item maintains a fixed distance of 60mm from the outer casing of the chimney to the wall or fixing point.

  1. Once the position of the support has been determined, secure the back bracket to the wall with a method of fixing to ensure adequate attachment and support.
  2. The stainless steel split band is then positioned around the chimney section and secured with the nuts and bolts provided to the back bracket.
  3. The wall bracket provides lateral stability only, it is NOT load bearing and is to be positioned at 3 metre centres.

Adjustable Back Bracket (60-300mm)

Internal and External Application

The adjustable wall bracket is supplied in three parts, a ‘U’ shaped stainless steel adjustable section, two bolts for fixing the wall band to the back bracket and a strengthening cross bracket.

  1. Once the position of the support has been determined, secure the U shaped bracket to the wall with a method of fixing to ensure adequate attachment and support.
  2. Determine the amount of extension required and secure the back bracket of the wall band in place onto the adjustable section.
  3. Fasten the strengthening cross bracket in place using the bolts provided.
  4. With the back bracket in place, locate the rear portion of the band onto the back bracket, the outer part of the band is then positioned around the chimney section and secure with the nuts and bolts provided.
  5. The adjustable wall band provides lateral stability only, it is NOT load bearing and is to be positioned at 3 metre centres.

Int 0

100

125

150

I80

200

Ext 0

150

I80

200

235

256

(mm)

131

131

I48

I85

202

(mm)

83

112

132

162

I86

(mm)

25

25

25

25

25

Wall Band and Adjustable Back Bracket Assembly

Structural Wall Band (50mm)

The structural wall band is supplied in two parts, a stainless steel split band which fits tightly around the outside of the chimney and a stainless steel back bracket The parts are joined together by means of the nuts and bolts provided. The use of the item maintains a fixed distance of 50mm from the outer casing of the chimney to the wall or fixing point. It can be used in combination with the structural wall band extension components to provide for adjustment to various distances from the wall. B

  1. Once the position of the support has been determined, secure the back bracket to the wall with a method of fixing to ensure adequate attachment and support.
  2. The stainless steel split band is then positioned around the chimney section and secured with the nuts and bolts provided to the back bracket.
  3. The wall bracket provides lateral stability only, it is NOT load bearing and is to be positioned at maximum 4 metre centres.

Int 0

100

125

150

I80

200

Ext 0

150

I80

200

235

256

(mm)

126

144

164

194

214

(mm)

55

55

55

55

55

Structural Wall Band Extensions

Available in 3 different sizes. Type W1 gives adjustment of between 55-I00mm from the wall. LI gives adjustment of between I00-250mm from the wall and L2 gives adjustment of between I00-440mm from the wall.

  1. Once the position of the support has been determined, secure the back bracket to the wall with a method of fixing to ensure adequate attachment and support.
  2. Fasten the structural wall band to the extension brackets using the nuts and bolts provided.

Int 0

80

100

130

150

I80

200

230

250

300

Ext 0

130

150

I80

200

230

250

280

300

350

C

174

194

224

244

274

294

324

344

394

D

E

I80

110

200

110

230

110

250

110

280

110

300

110

330

110

350

110

400

110

Base support Plate with Drain

This component is used to support the chimney directly from the floor. It should be fastened securely to the floor using bolts or screws provided by others.

Load bearing supports

All wall supports and floor supports are designed to provide load bearing support for the chimney. They must be used in combination with the relevant lateral support components, wall bands, guy wire brackets or telescopic roof stays as appropriate.

Retrofit wall support

  • Lower the clamp band over the pipe length with the joint facing the wall.
  • On the joint, ensure that the spring washer is between the plain washer and the bolt head.
  • Tighten the two fixing bolts on the clamp band using a torque wrench up to a minimum of 10 Nm (Newton-Meters).
  • Attach the side brackets to the fixing bolts on the side of the band, but don’t tighten.
  • Attach the side brackets to the wall using a method of fixing to ensure adequate attachment and support, i.e. shield anchors.
  • Mark up the hole positions for the brackets on the wall.
  • Fix the brackets to the bolts on the side of the clamp band using the locking nuts provided.
  • For maximum height of chimney see load bearing details on p. 41.

Adjustable Top Plate

The wall support is designed to be used internally or externally to provide either initial or intermediate support for the vertical chimney. It is used in combination with side plates or with cantilever brackets. The turned down edge at the front of the plates is slotted to allow for the plate to slide along the cantilever brackets and give some positional adjustment. The female socket on the pipe attached to the underside of the plate should be pushed down onto the preceding pipe and the joint secured using the locking band provided.The top plate is then attached to the side plates or the cantilever brackets using the bolts provided through the fixing slots in the top plate (see Fig. 1). The bolts should then be tightened firmly.

Int 0

100

125

150

I80

200

Ext 0

150

I80

200

235

256

(mm)

266

276

296

334

352

(mm)

247

287

307

342

363

(mm)

127 142 152 170 180

(mm)

106 106 106 105 108

Side Plates/Cantilever Brackets

Once the position of the support has been established in relation to the chimney route, secure the side plates or cantilever brackets to the wall using expansion bolts to ensure adequate attachment and support (see Fig. 2).

Int 0

100

125

150

180

200

(mm)

235 275 295 325 345

(mm)

165 160 180 210 230

(mm)

470 470 470 470 470

(mm)

100 100 100 100 100

Cantilever Supports

Type

325

475

570

0 Range

125-200

125-200

125-200

(mm)

325

475

570

(mm)

242

242

242

Cantilever Support Adjustment

 

 

Cantilever Support Adjustment
Int Ø 100 125 150 180 200
C max
Type 325 164 134 114 84 64
Type 475 314 284 264 234 214
Type 570 409 379 359 329 309
Type 720 559 529 509 479 459
Type 820 659 629 609 579 559
Type 1004 843 813 793 763 743
Type 1120 959 929 909 879 859
C min
All Types 50 50 50 50 50

G50 Ceiling Joist Support

The joist support can be used in 2 different ways: Option 1 – where the chimney passes through a combustible ceiling into the roof space, and the weight of the chimney has to be taken at floor level. The ceiling joist support must be firmly fixed by using bolts or screws. For load bearing Data refer to tables I and 2 on page 33. (as per Ventilated Support Plate)

  1. Frame a four sided level square opening within the joists using timber stringers where necessary to allow for the correct distance to combustibles from the outer wall of the chimney. This distance must be a minimum of 50mm on Gas and Oil applications and 60mm for solid fuel applications (see Fig. 3 alongside – distance x).
  2. Lower the chimney section through the opening in the floor, and secure to the next section of pipe.
  3. Locate the two halves of the support plates around the chimney section, and secure to the joists using screws or bolts.
  4. Remove the self-drilling screws which are fastened to the clamp band.Then fasten clamp band around the chimney section and position on top of the plate. Tighten using the nuts and bolts provided.
  5. Using the holes in the clamp band as a guide, fasten the three self-drilling screws to the outer case of the ICID Plus system.

Note: Joints must NOT occur within the floor or ceiling joists.

Option 2 – Install as per option I, but rather than use wooden stringers between the joists, use the ceiling joist support arms, which are fixed to the joists using the screws provided. The plate is then attached to the support arms using the nuts and bolts provided.

Roof Support

The roof support is supplied as a kit complete with two side plates for fixing to the roof trusses, a band to give lateral support to the chimney as it passes through the roof, and 3 self tapping screws, which are secured to the chimney through the band to give a load bearing capacity. When the plates are installed above the roof trusses as in Fig.1 the maximum number of pipes, which may be suspended from the roof support is 6 x 1m pipes. When the plates are attached below the trusses as in Fig.2 the maximum number of pipes, which may be suspended is 4 x 1m pipes. I. The band should be lowered down over the top of the ICID Plus pipe, and positioned so that the the side plates are resting on top of the roof trusses as in Fig.1 or below the roof trusses in the case of Fig. 2.The recommended position

  1. is always as per Fig.1 where circumstances allow this solution.
  2. The band should then be tightened using the nut and bolt provided. Using the holes pre-drilled in the roof support band, drill 3mm holes in the outer case of the chimney section (drill bit should be set for a depth no greater
  3. than I0mm to avoid any damage to the liner of the chimney)

Use the self tapping screws provided to secure the clamp band to the outer casing of the chimney section. Please note: It is the responsibility of the installer to ensure that the joist to which the roof support is being attached is load bearing and capable of withstanding the weight of the system being installed.

Guy Wire Bracket

This component should be used to secure unsupported chimney sections above roof level. Guy wires or preferably rigid stays (supplied by others) must be fixed to the bracket and secured to suitable anchorage points to ensure that the chimney sections are stable. A maximum chimney height of I.5 metres from the last support, or from the roof is permitted. Additional height requirements MUST be supported at I.5 metre intervals using the guy wire bracket as specified above.

Telescopic Roof Stays The telescopic roof stay kit has been added to the range to allow for extra support on chimneys above roof level, where standard guy wires can not be fitted. The telescopic legs allow for height adjustment from 1.6m-2.5m

Ceiling Hanger

This accessory is designed to support horizontal runs of the chimney from the roof or ceiling and offers adjustment from I30mm to III5mm.

  1. I. Once the position of the ceiling support has been determined, the section length of unirax channel must be securely fixed to the roof or the ceiling using a method of attachment to ensure adequate attachment and support.
  2. All items are assembled as shown to attach the length of studding to the channel.
  3. Attach the stud connector to the length of studding and connect the eye bolt to the connector.
  4. Position the split band around the chimney section and secure to the eye bolt using the nut/bolt provided.
  5. Maximum support spacing to be no more than I.5 metres.

Wall sleeve (90° & 135° variants)

Wall sleeves must be used to protect the building where the chimney passes through a wall (see Fig. 2 & 3). The 90° version is supplied as a straight length whereas the 135° version is mitred at 45 degrees on one end. The sleeve should be cut down to the correct length on site to fit flush with the wall (see Fig. 1 & 2). The sleeve should be adequately weatherproofed, using a good quality building mastic and rope fibre.

Two Piece Trim Collar (90° & 135° variants)

Two piece trim collars are fitted around the ICID Plus pipe where it protrudes through both the inside and the outside of the wall (see Fig. 1 & 2). They should be fastened to the wall using an adequate method of fixing. The trim collars should be adequately weatherproofed back to the wall and around the chimney, using a good quality building mastic or equivalent.

Angled Flashing

Manufactured in sheet aluminium for use on pitched roofs. The base of the flashing should be nailed or screw fixed to the roof batons prior to tiling. The front edge of the flashing should be hooked to the underside of the batons to prevent lifting. This component should be sealed with the mastic sealant provided and MUST be used in conjunction with the storm collar supplied.

Flat Flashing

Manufactured in sheet aluminium for use on flat roofs the base of the flashing should be covered by the roofing felt and then sealed.This component should be sealed with the mastic sealant provided and MUST be used in conjunction with the storm collar supplied.

Storm Collar

The storm collar should be sealed to the outer casing of the flue immediately above the flashing with the mastic sealant provided.

Uniflash

This item, which is manufactured with a malleable base and a silicone cone is used to provide a water tight flashing around the chimney as it passes through a roof pitched between 0-45 degrees.The cone is marked with pipe diameter sizes.

  1. Cut the cone to suit the correct diameter of chimney.
  2. Slide the flashing down over the top of the pipe and then form the base to the shape of the roof surface.
  3. Seal as required.

Ext 0

125-150

180-200

(mm)

500

685

Ignis-Protect

https://youtu.be/nd07eRzb7yg Ignis Protect is designed specifically for Air Tight, Energy Efficient and Timber Framed Buildings PRODUCT FEATURES

  • Suitable for SW and DW connecting flue pipes passing through interior or exterior walls made of combustible materials
  • Available in two versions:
    • For exterior walls
    • For interior walls
  • Available in both 90° and 45° versions
  • For flue gas temperature up to:
    • 450 °C for SW connecting flue pipes (T450)
    • 600 °C for DW connecting flue pipes(T600)
  • Max. 100 °C surface temperature during soot fire
  • Monolithic component made of mineral wool, density 120 kg/m³, building material class A1
  • Internal face finished with aluminium laminate
  • External face made with textured surface to facilitate façade rendering
  • Removable pipe sections DN 125, 130, 150, 180, 200 mm
  • IGNIS-PROTECT can be used without any additional protection
  • Available in a range of standard wall thicknesses between 100mm -500mm

Window and door lintels and their support areas, as well as other bearing elements must not be weakened! In case of uncertainty consult a structural engineer


1. Clear installation width required is 565mm.


2. Clear installation height of 700mm on 90° version,1020mm on 45° version for walls between 100 – 200mm thick, and height 1320mm on walls between 250 – 500mm thick


3. Remove plasterboard. NOTE: The vapour barrier must not be damaged!


4. Cut a cross shape in the vapour barrier to the required dimensions of the opening (see figs. 1. and 2.)


5. Make the opening. NOTE: Bearing elements must not be weakened! IMPORTANT: follow the safe working notes on page 29


6. Remove wood fibre board, thermal insulation etc. from the assembly opening.


7. Install the wooden surround for Ignis-Protect into the studwork


8. Check width of the opening: 565mm


9. Check height of the opening (see image 2.)


10. If necessary correct the opening. Replace the thermal insulation right around the assembly opening in the studwork. IMPORTANT: follow the safe working notes on page 29.


11. Open up the exterior wall. TIP No gaps should be left in the studwork or the surrounding thermal insulation!


12. Insert Ignis-Protect so that it fits perfectly. The side laminated with foil should be facing inwards!


13. With Ignis-Protect in place, cut away the vapour barrier flush to the edges


14. Secure the junctions with the vapour barrier by applying appropriate sealing tape to the foil lamination.


15. View of the finished vapour barrier sealed tightly all round.


16. Cut a hole in the thermal board to fit the Ignis-Protect outer protection pipe. IMPORTANT: follow the safe working notes on page 29.


17. Replace the prepared thermal board. NOTE: The vapour barrier must not be damaged!


18. The Ignis-Protect inner protection pipe and the outer protection pipe are basically designed for 24mm wall planking. If necessary, shorten the inner and outer protection pipes to be flush with the wall. IMPORTANT: follow the safe working notes on page 29.


19. By pulling out the corresponding inner protection pipes and the assembly cap (A) the connection size is adapted to fit the required connecting pipe or transition piece. The inner protection pipes and the assembly cap (A) remain in place until the stove connection pipe is in its final position in the Ignis-Protect.


20. Check that the thermal insulation is flush with the wall. Follow the preparation guidelines and relevant drying times of the render system manufacturer!


21. Application of render over the whole surface. NOTE: do not render over the inner protection pipe


22. Example of a design with a double walled connecting flue pipe.


23. Finished installation.


HEALTH & SAFETY INSTRUCTION Many building products, including chimney elements are manufactured using natural raw materials which contain proportions of crystaline quartz. During the mechanical processing of products, such as cutting and drilling, quartz dust is released which can get into the lungs. With higher levels of exposure over longer periods this may result in damage to the lungs (silicosis) and as a consequence of the silicosis disease, to an increased risk of lung cancer. THE FOLLOWING PROTECTIVE MEASURES ARE TO BE TAKEN

  • When cutting and drilling, a P3/FFP3 respiratory protection mask is to be worn.
  • In addition, wet-cutting equipment or equipment with dust extraction should be used.

Protection measures are required when cutting and drilling. Wet-cutting or dust extraction should be used.

  • Eye Protection
  • Ear Protection
  • P3/FFP3 Respiratory Protection Mask

HAZARDS FOR PEOPLE AND THE ENVIRONMENT Mineral wool insulation materials in this group of products can release fine fibres which may have carcinogenic effects in the lungs. If inhaled, fibres can get into the body and cause damage to health. Larger fibres or fragments of fibres can cause irritation (itching) of the skin, the upper airways and the eyes! PROTECTION MEASURES AND SAFE PRACTICE Avoid contact with the skin! After finishing work, rinse off dust with water and change your clothes. wash exposed areas of skin thoroughly with soap and if necessary use a skin care product!

  • Eye Protection: When working overhead and where large amounts of dust are produced, wear goggles with side protection.
  • Hand Protection: Protective gloves, e.g. in leather or nitrile-coated cotton.
  • Breathing: For low-level activities (exposure category E1/E2) the use of half or quarter masks with P2 filters (white) or FFP2 particle filtering half masks is recommended.

Protect Box

New Housing Air Tightness Requirements

Schiedel provide an air tight sealing kit to prevent leakage where the chimney passes through vapour and/ or wind barriers. This sealing kit is used in conjunction with our ICSSO System Chimney. The use of 5Omm insulation ensures that the outer skin temperature on the chimney remains low enough for the EPDM kit

Installation

Schiedel airtight kits are tailored to meet the outer diameter of Schiedel’s twin wall insulated ICSSO System Chimney. The kit is pulled around the outer case of the ICSSO System Chimney and attached to the air tight membrane, using the special tape provided.

Sealing Tape

The special tape used with the airtight kit is made from elastic PE film and acryl adhesive. This combination means the tape is long-lasting and quick to fit (it sticks immediately).To make it as easy to use as possible, the tape comes with a paper liner which is removed prior to use. N.B. Do not use tape on steel pipe, only to seal the joint between the EPDM seal and the vapour/wind barriers.

Application

The tape is used to attach the EPDM seal to the vapour and/or wind barriers. Schiedel Chimney Systems Ltd does not advise using the tape on rough surfaces, concrete, brick or bitumen-based materials. Surfaces must be clean, dry and grease-free before fitting.

Terminals

Terminals are supplied complete with a locking band. Once the terminal has been pushed into place, the adjustment bolt on the locking band clip should be tightened to ensure that the terminal is properly secured to the previous pipe.

OUTLET SITING

Flue terminations for solid fuel & oil are subject to ENI5287-I. Figures A and B illustrate recommendations for the most commonly encountered outlet terminations. Flue terminations for gas in domestic situations are governed by the BS5440-I Section 4.2. Figure C illustrates recommendations for the most common siting situations encountered. Adjacent taller structures may require increased height. The minimum flue projection through the roof is 600mm to the underside of the terminal.

Outlet siting for Oil Appliances (<45kW)

Location of outlet

Pressure Jet Burner

Vapourising Burner

M

Above the highest point of an intersection with the roof

600mm

1000mm

N

From a structure to the side of the terminal

750mm

2300mm

O

Above a vertical structure which is less than 750mm (pressure jet burner) or 2300mm (vapourising burner) horizontally from the side of the terminal

600mm

1000mm

P

From a ridge terminal to a vertical structure on the roof

1500mm

Should not be used

Outlet siting for Solid Fuel Appliances (<50kW)

 

Point where flue passes through weather surface (Notes I, 2)

Clearance to flue outlet

A

At or within 600mm of the ridge

At or within 600mm above the ridge

B

Elsewhere on the roof (whether pitched or flat)

At least 2300mm horizontally from the nearest point on the weather surface and:

C

Below (on a pitched roof) or within 2300mm horizontally to an openable rooflight, dormer window or other opening (Note 3)

At least I000mm above the top of the opening

D

Within 2300mm of an adjoining or adjacent building, whether or not beyond the boundary (Note 3)

At least 600mm above any part of the adjacent building within 2300mm

  1. The weather surface is the building external surface, such as its roof, tiles or external walls.
  2. A flat roof has a pitch less than I0°.
  3. The clearance for A or B, as appropriate, will also apply.
  4. A vertical flue fixed to an outside wall should be treated as equivalent to an inside flue emerging at the nearest edge of the roof.

TYPICAL EXTERNAL INSTALLATIONS

Int Ø (mm)

(m)

(m)

(m)

(m)

100

3

22

15

4

125

3

22

15

4

150

3

18

15

4

180

3

18

15

4

200

3

18

15

4

LOAD BEARING DATA

Maximum Load Bearing (metres of pipe)

Internal Diameter (mm)

100

125

150

180

200

Internal Diameter (mm) 100 125 150 180 200
Base Drain Section 22 22 18 18 18
Retrofit Wall Support 10 10 10
Top Plate and Locking Band 15 15 15 15 15
Pair or Side Plates (see diagram A) 15 15 15 15 15
Pair or Side Plates (see diagram B) 10 10 10 10 10
Cantilever Support 22 22 18 18 18
Extension Support (Anchor Plate) 1.5 1.5 1.5 1.5 1.5
Ventilated Support Plate (All types) 12 12 12 12 12
Ceiling Joist Support 12 12 12 12 12
Support Plate 12 12 12 12 12
Wall Band 50mm 3 3 3 3 3
Adjustable Wall Band 75-300mm 3 3 3 3 3
Structural Wall Band 4 4 4 4 4
Extension for Structural Wall Band 4 4 4 4 4
Roof Support (above truss) 6 6 6 6 6
Roof Support (below truss) 4 4 4 4 4
Guy Wire Bracket 1.5 1.5 1.5 1.5 1.5
90° Tee + Locking Band 22 22 18 18 18
135° Tee + Locking Band 15 15 10 10 10
Inspection Tee (Rectangular) 22 22 18 18 18

COMPONENT WEIGHTS

Int. Diameter Length(mm)

1460

960

460

293

160

100mm

5.78

4.18

3.64

3.32

125mm

11.9

7.1

3.7

2.3

1.5

150mm

12.9

7.9

4.2

2.6

1.8

180mm

16.5

9.8

5.1

3.4

2.2

200mm

17.8

10.6

5.5

3.7

2.3

 

AFTER INSTALLATION

Testing and Commissioning prior to irst use

This is carried out using a flue flow test as described in BS EN 15287 Parts 1 & 2, with reference to the appropriate appliance type.

Appliance Operation

Appliance slumbering must be avoided, and if the appliance has been run on low fire conditions for an extended period, then it is advisable to run the appliance at controlled high fire condition for a minimum period of at least 30 minutes afterwards. Prolonged slumbering of the appliance at all times is a contributing factor to a system chimney failure. It is important to maintain sufficiently high flue gas temperatures in order to avoid condensate and acid corrosion problems, and to ensure complete combustion of the fuel at all times. If corrosion occurs due to slumbering, then the guarantee will be invalidated on the system.

Multi-Fuel Applications

Multi-Fuel refers to an appliance which may be used to burn either seasoned wood, or approved solid fuels.These fuels should not be mixed, as this increases the risk of deposits being built up in the liner.

Maintenance

Each chimney must be designed to allow for easy inspection; sweeping should be carried out by competent persons. On solid fuel applications a list of HETAS registered sweeps can be found at www.hetas.co.uk. Chimney flue cleaning and inspection require the use of appropriate tooling – under no circumstances should chemical cleaners or mild steel tools be used to sweep stainless steel chimneys. Cleaning/inspection of any chimney system should be carried out at least once a year, along with maintenance of the appliance, but it is recommended that chimneys serving solid fuel appliances be swept at least twice a year, at the end of the heating season to remove any deposits, which may have built up during the season, and prior to the start of the next heating season to ensure that the the flue way is clear of any blockages such as birds nests etc. We would advise that monthly checks are carried out to ensure that there is no build up of any deposits in the flue way of the connecting flue pipe or system chimney.

Fuel Storage and Usage

Where solid fuels are being used, correct storage is critical and fuels must be kept dry. Wood must be seasoned prior to use, with a maximum moisture content of 20%. Only approved fuels should be used. Refer to HETAS list for details on www.hetas.co.uk.The fuel used must be suitable for the appliance – please refer to manufacturer’s instructions.

NOTICE PLATE

Notice Plate for ICID Plus Product

The Notice plate should be marked up in indelible ink and securely fixed in an unobtrusive but obvious position within the building such as:

  • Next to the electricity consumer unit.
  • Next to the chimney installation described.
  • Next to the water supply stop-cock.

See example alongside:

PRODUCT GUARANTEE

We are confident in our products and so offer you (the owner) a generous warranty in relation to the ICID Plus system (the System). Provided that you comply with the conditions stated below, the system will be free from defects for whichever is the greater of:

  • a period equal to the guarantee period of the appliance to which the Liner is first connected; or
  • 20 years.

The conditions of the guarantee are:

  • Correctly sized and installed in accordance with the manufacturer’s instructions, current Building Regulations and relevant British and European standards.
  • Maintained correctly by a qualified and competent person and maintenance records kept updated for both appliance and chimney/chimney liner.
  • Used in combination with an appliance burning only approved fuels in accordance with Schiedel Chimney Systems and the appliance manufacturer’s instructions.
  • Register your product within 30 days of installation at www.schiedel.co.uk and provide us with any evidence we reasonably request to prove that your System has been fitted by a HETAS approved installer or if not, has been signed off by a Building Control Inspector prior to use.
  • Familiarise yourself with the installation instructions and comply with its provisions in full during the lifetime of your usage of the product (including by keeping the required records safe). Failure to do so will invalidate any guarantee claim.

For more details about the guarantee visit our website.

For recommended fuels listings, please refer to the HETAS Guide www.hetas.co.uk

In the event of a fault developing in the product due to defective materials or faulty manufacture Schiedel Chimney Systems undertake to replace the product only. Schiedel Chimney Systems cannot accept liability nor take any responsibility for the installation, building or redecorating costs or any other consequential losses arising. If any complaint is found to be a result of faulty installation, non-compliance with or abuse contrary to these conditions, the cost of site investigation is chargeable

Product Registration

We have upgraded our guarantee registration system. This is only available online. Visit www.schiedel.com to register.

Please Note: An incomplete registration could make your warranty void.

Don’t forget to post pictures of your installation on social media and tag @schiedelUK– you could even be featured as a case study!